PR Electronics 9100 Series Temperature Converter, Current, RTD, Thermocouple Input, Current, Relay Output, 19.2
- RS Stock No.:
- 796-7048
- Mfr. Part No.:
- 9113BB
- Manufacturer:
- PR Electronics
7 In stock for delivery within 6 working days
Added
Price (VAT excluded) Each
TWD24,298.00
(exc. GST)
TWD25,512.90
(inc. GST)
Units | Per unit |
1 + | TWD24,298.00 |
- RS Stock No.:
- 796-7048
- Mfr. Part No.:
- 9113BB
- Manufacturer:
- PR Electronics
Product overview and Technical data sheets
Legislation and Compliance
- COO (Country of Origin):
- DK
Product Details
9113B Type - Ex Temperature / mA Converter
The 9113B is a temperature- and mA converter with 1- or 2-channels. The converter has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
Features and Benefits
Ex temperature / mA converter for input for RTD, TC and mA
1-channel version, stock-no. 796-7045
2-channel version, stock-no. 796-7048
Conversion and scaling of temperature (Pt, Ni and TC) and active current signals
TC inputs can use either the internal CJC or a terminal with a built-in Pt100 sensor (PR 5910Ex, channel 1 / PR 5913Ex, channel 2) for higher accuracy
Active / passive mA output
SIL 2-certified via Full Assessment, the functionality is optional and must be activated in a menu point
Configuration and monitoring by way of detachable display front (PR 4501); process calibration and signal simulation
Copying of the configuration from one device to others of the same type via the display front
Please order the Display Front PR4501 separately (stock-no. 796-6890)
The device can be mounted in the safe area and in zone 2 / cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G
Front LEDs indicate operation status and malfunction
2.6 kVAC galvanic isolation between input, output and supply
Can be supplied separately or installed on power rail, PR type 9400
1-channel version, stock-no. 796-7045
2-channel version, stock-no. 796-7048
Conversion and scaling of temperature (Pt, Ni and TC) and active current signals
TC inputs can use either the internal CJC or a terminal with a built-in Pt100 sensor (PR 5910Ex, channel 1 / PR 5913Ex, channel 2) for higher accuracy
Active / passive mA output
SIL 2-certified via Full Assessment, the functionality is optional and must be activated in a menu point
Configuration and monitoring by way of detachable display front (PR 4501); process calibration and signal simulation
Copying of the configuration from one device to others of the same type via the display front
Please order the Display Front PR4501 separately (stock-no. 796-6890)
The device can be mounted in the safe area and in zone 2 / cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G
Front LEDs indicate operation status and malfunction
2.6 kVAC galvanic isolation between input, output and supply
Can be supplied separately or installed on power rail, PR type 9400
Programming
The 9113B universal transmitters are programmable via the PR 4510 detachable display module (238-0641). The 4510 module allows the programming of the vast array of input and output parameters easily and safely. Together with advanced functions including 2-point calibration, process simulation and diagnostics.
With a simple menu and explanatory text, the 4510 is extremely straightforward to navigate. Functions are clearly depicted on the 4-line LCD display even in low light conditions. Line 1 shows the input signal, line 2 shows the units, and line 3 shows analogue output or tag number. Line 4 shows the communication and relay status. In addition, the 4510 features password protection. Programming access can be blocked by assigning a password which is conveniently saved in the 9113B transmitter. This ensures a high degree of protection is maintained and prevents any unauthorised modifications to the configuration.
With a simple menu and explanatory text, the 4510 is extremely straightforward to navigate. Functions are clearly depicted on the 4-line LCD display even in low light conditions. Line 1 shows the input signal, line 2 shows the units, and line 3 shows analogue output or tag number. Line 4 shows the communication and relay status. In addition, the 4510 features password protection. Programming access can be blocked by assigning a password which is conveniently saved in the 9113B transmitter. This ensures a high degree of protection is maintained and prevents any unauthorised modifications to the configuration.
PR Electronics - Ex Interfaces
Specifications
Attribute | Value |
---|---|
Module Type | Temperature Converter |
Input Signal Type | Current, RTD, Thermocouple |
Output Signal Type | Current, Relay |
Supply Voltage | 19.2 → 31.2V dc |
Hazardous Area Certification | ATEX |
Operating Temperature Range | -20 → +60°C |
Series | 9100 |
Maximum Operating Temperature | +60°C |
Minimum Operating Temperature | -20°C |