Product Details
ABB Monitoring Relay, 380V AC Control Voltage Rating, 0 to 30s Adjustable Time Delay - CM-PSS Series - 1SVR730784R2300 CM-PSS.31S
Spot power faults as soon as they pop up with this monitoring relay from ABB. By tripping a circuit breaker if it senses an issue, it helps stop problems in their tracks to cut the risk of hardware damage. As the device checks for overvoltage, undervoltage and phase failure, it provides comprehensive fault detection to let you rest easy. Support for tool-free DIN rail mounting snaps the unit into place in no time. Thanks to the product's adjustable time delay between 0 and 30s, there's no need for expected overvoltage to grind your process to a halt.
Features & Benefits
Compact dimensions of 103.7 (L) x 22.5 (W) x 85.6mm (H) easily fit into a small enclosure
Screw-clamp terminals to stop disruption from movement
Wide voltage monitoring range between 342 and 418V AC, so it works with many standard power sources
Front-mounted LED indicators clearly show circuit status for quick spot checks
Screw-clamp terminals to stop disruption from movement
Wide voltage monitoring range between 342 and 418V AC, so it works with many standard power sources
Front-mounted LED indicators clearly show circuit status for quick spot checks
Applications
Industrial automation
HVAC systems
Water treatment works
HVAC systems
Water treatment works
How do I adjust the time delay on this product?
You can control this relay's time delay by turning the screw dial on its front plate, making it easy to adjust to fit your system.
Specifications
Attribute | Value |
---|---|
Monitoring Application | Phase, Voltage |
Electrical Phase | 3 |
Contact Configuration | DPDT |
Voltage Sensing Range | 342 → 418V ac |
Voltage Sensitivity | Overvoltage, Undervoltage |
Mounting Type | DIN Rail |
Phase Sensitivity | Phase Failure, Phase Sequence |
Time Delay | 0.1 → 30 s, 0s |
Frequency Sensing Range | 45 → 65Hz |
Series | CM-PSS |
Width | 22.5mm |
Maximum Operating Temperature | +60°C |
Current Range | 2 → 4A |
Standards Met | UL |
Dimensions | 103.7 x 22.5 x 85.6mm |
Minimum Operating Temperature | -25°C |
Terminal Type | Screw |
Operating Temperature Range | -25 → +60°C |
Maximum Voltage Sensed | 418V ac |
Length | 103.7mm |
Height | 85.6mm |
Minimum Voltage Sensed | 342V ac |