PR Electronics 3100 Series Bipolar Isolated Converter, Current, Voltage Input, Current, Voltage Output, 16.8 →
- RS Stock No.:
- 796-7098
- Mfr. Part No.:
- 3117
- Manufacturer:
- PR Electronics
- RS Stock No.:
- 796-7098
- Mfr. Part No.:
- 3117
- Manufacturer:
- PR Electronics
Product overview and Technical data sheets
Legislation and Compliance
- COO (Country of Origin):
- DK
Product Details
3100 Type - Bipolar Isolated Converter
3117 and 3118 types are for isolation and conversion of standard current and voltage signals.
Suitable for galvanic separation of analog current and voltage signals and elimination of ground loops and measurement of floating signals.
Suitable for galvanic separation of analog current and voltage signals and elimination of ground loops and measurement of floating signals.
Features and Benefits
Converter for current and voltage bipolar process signals to unipolar signals
Response time < 7 ms
Splitter function: 1 in - 2 out (only 3118 type, stock-no. 796-7092)
Multiple signal ranges are selectable via DIP-switches
Excellent accuracy, better than 0.05 % of selected range
All terminals are protected against overvoltage and polarity error
High galvanic isolation of 2.5 kVAC
Response time < 7 ms
Splitter function: 1 in - 2 out (only 3118 type, stock-no. 796-7092)
Multiple signal ranges are selectable via DIP-switches
Excellent accuracy, better than 0.05 % of selected range
All terminals are protected against overvoltage and polarity error
High galvanic isolation of 2.5 kVAC
DIP-switch programming
Re-calibration is not needed after changing the DIP-switch range settings. Just change the DIP-switch, cycle the power to the unit and obtain the new, pre-calibrated I/O range. HART programming is enabled for selected devices.
Mounting
Devices can be mounted both vertically and horizontally with no air gap separation required. The devices snap onto a power rail or DIN rail and are easily detached by lifting the bottom lock.
High level of isolation
Safe galvanic isolation of 2.5 kVAC provides high noise immunity and prevents ground loops for accurate delivery of the process signal to your control system.
Device status indicators
A front LED indicates device status, e.g. an error in the set-up, sensor or hardware.
Over voltage- / polarity protection
All terminals can withstand up to ±31.2 VDC and are protected against incorrect supply wiring to ensure safe, error-free installation.
For products that are Customized and under Non-cancellable & Non-returnable, Sales & Conditions apply.
PR Electronics DIN Rail Mounting
Specifications
Attribute | Value |
---|---|
Module Type | Bipolar Isolated Converter |
Input Signal Type | Current, Voltage |
Output Signal Type | Current, Voltage |
Input Range | -11.5 → 11.5 V, -23 → 23mA |
Output Range | 0 → 11.5 V, 0 → 23mA |
Supply Voltage | 16.8 → 31.2V dc |
Hazardous Area Certification | ATEX |
Mounting Type | DIN Rail Mount |
Operating Temperature Range | -25 → +70°C |
Series | 3100 |
Maximum Operating Temperature | +70°C |
Minimum Operating Temperature | -25°C |